STUDER BETAflam® Solar 125 flex WR 1500 Photovoltaic power cables, halogen-free, flame retardant (Water Resistant)

Previous 2 / 3 Next

STUDER BETAflam® Solar 125 flex WR 1500 Photovoltaic power cables, halogen-free, flame retardant (Water Resistant) Photovoltaic systems (Solar Cable)


STUDER BETAflam® Solar 125 flex WR 1500 (Water Resistant)

Photovoltaic power cables, halogen-free, flame retardant

Applications

Special water resistant and tested according to TÜV Rheinland,
Germany: 2Pfg 2750/09.20 for floating PV applications (FPV).
 

Construction

Conductor       :   Tinned fine copper strands, acc. to VDE 0295 / IEC 60228, class 5
Insulation        :   XLPO, flame retardant, halogen-free, electron-beam cross-linked
Jacket              :   XLPO, flame retardant, halogen-free, electron-beam cross-linked, UV and ozone resistant
Jacket colour  :   Black
 
 

Benefits

•   TÜV Rheinland, Germany: 2Pfg 2750/09.20, EN 50618, IEC 62930 certification
•   Water resistant tested acc. to UL standards
•   Electron-beam cross-linked compounds
•   UV, ozone and hydrolysis resistant
•   High temperature resistance, the materials do not melt or flow
•   Very long service life¹, good cold flexibility
•   Compatible to all popular connectors
•   Direct burial

Electrical properties

Rated value      :  U₀   1500 V DC (max. permitted voltage U₀ 1800 V DC)
 

Thermal properties

Operating temperature  :   − 40 °C up to + 120 °C
                                              − 40 °F up to + 248 °F
 
Ambient temperature    :   − 40 °C up to + 90 °C
min. 25 years¹                      − 40 °F up to + 194 °F
 
Max. short circuit           :   + 280 °C / 5 s
temperature                         + 536 °F / 5 s
 

Bending radius

Fixed installation          :   > 4 × outer Ø
Occasionally moved      :   > 5 × outer Ø
 

Standards / Material properties

Fire performance          :   IEC 60332-1
Smoke emission             :   IEC 61034; EN 61034-
Low fire load                 :   DIN 51900
Approval                        :   TÜV 2Pfg 2750/09.20; EN 50618; IEC 62930
 
 