STUDER BETAflam® Solar 125 RV+ flex 1500V DC PHOTOVOLTAIC STRING AND MODULE CABLES H1Z2Z2-K

Previous 3 / 3 Next

STUDER BETAflam® Solar 125 RV+ flex 1500V DC PHOTOVOLTAIC STRING AND MODULE CABLES H1Z2Z2-K Photovoltaic systems (Solar Cable)


Application 

Is used as photovoltaic cable between solar modules and inverters in a photovoltaic system with a rated voltage U₀ = 1.5 kV DC.
 

Construction

Conductor       :  Tinned fine copper strand acc. to VDE 0295 / IEC 60228, class 5
 
Insulation        :  Polyolefin, HFFR compound,electronbeam cross-linked
 
Sheath              :  Polyolefin, HFFR compound, electronbeam cross-linked
 
Sheath colour  :  Black with white or red marking and stripe
 

Advantages

•   EN 50618, IEC 62930 approval
•   Electron-beam cross-linked compounds
•   UV, ozone and hydrolysis resistant
•   Very high resistance to temperature
•   High CPR fire performance Cca
•   Very long service life > 25 years at 90 °C
•   Compatible to all popular connectors
 

Electrical properties

Rated voltage            :  U0 1500 V DC
Maximum voltage    :  U0m 1800 V DC
Test voltage               :  6.5 kV, 50 Hz / 5 min.
 

Thermal properties

Max.operating temperature       :  +120°C
Min. ambient temperature         :  -50°C
Max. ambient temperature        :  +90°C
Max. short circuit temperature :  +280°C (max. 5s)
 

Mechanical properties

Bending radius  : fixed installation ≥ 4 x Ø
Bending radius  : occasionally moved ≥ 5 x Ø
 

Material properties / Standards

Fire Performance                                                                        :  IEC 60332-1
Smoke emission                                                                           :  IEC 61034; DIN EN 61034-2
Low fire load                                                                               :  DIN 51900
Fire properties acc. to CPR
Cca-s1a, d2, a1                                                                            :  DIN EN 50575;DIN EN 13501-6
Fire performance Cca                                                                :  DIN EN 50399
Very low smoke emission s1a                                                    :  DIN EN 50399
Flaming droplets d2                                                                   :  DIN EN 50399
Very low corrosivity of combustion gases – halogen free a1  :  DIN EN 60754-2
No flame propagation                                                                :  DIN EN 60332-1-2
 

Approvals

EN 50618; H1Z2Z2-K, IEC 62930
 